• Air-Quality Gas Sensor

ZP07-MP901 Air-Quality Detection Module

  • • 0-10 grade pollution signal
  • • Sensor: flat surface semiconductor gas sensor
  • • Application: air cleaner, fresh-air system, IAQ system

We're here to help: Easy ways to get the answers you need.

Share With:
Principle Introduction:
ZP07 air-quality module adopts flat surface semiconductor gas sensor. The module has good sensitivity to volatile organic gases such as formaldehyde, benzene, carbon monoxide, ammonia, hydrogen, alcohol and smoke of cigarette, essence &etc. The module has been aging, debugged, adjusted and calibrated. So it has good consistency and high sensitivity.
Applications :
Air cleaner, fresh-air system, intelligent integrated ceiling, air quality monitor, ventilator, air-condition.
Technical parameters :
Model ZP07-MP901
Sensor Air quality sensor
Target Gas formaldehyde, benzene, carbon monoxide, ammonia, hydrogen, alcohol, smoke of cigarette, essence &etc.
Physical Interface XH2.54-4P terminal sockets
Output Data 0-10 grade pollution signal
Working Voltage 5.0±0.2V DC (No voltage reverse connect protection)
Output Data TTL level (200ohm protected resistance inside)
Working Current ≤60mA
Warm Up Time ≤3 mins
Response Time ≤20s
Recovery Time ≤60s
Operating Temperature 0~50℃
Operating Humidity ≤95%RH
Storage Temperature -20~60℃
Storage Humidity ≤60%RH
Size 24×20×15mm(L×W×H)
Weight ≤ 20g
Sensitivity Attenuator ≤1%/year
Life Span ≥5 years


Reference Circuit :

Please fill in your procurement needs and contact information