Target: Liquefied
Model: MPn-5
Detection range: 300~5250 ppm
Detection principle: Semiconductor
Characteristics: High sensitivity to C3H8 gas


Get Price Whatsapp

Description

MPn-5 adopts a multi-layer thick film manufacturing process, which integrates a heating electrode, a measuring electrode and a metal oxide semiconductor gas sensitive layer on an Al2O3 ceramic substrate, and encapsulates it in a metal housing. When the detected gas is present in the ambient air, the conductivity of the sensor will change, and the higher the concentration of the gas, the higher the conductivity of the sensor. This change in conductivity can be converted into an output signal corresponding to the gas concentration using a simple circuit. The product has good anti-interference ability to common gases such as alcohol and acetic acid in the use scene.

Application

It is widely used in liquefied gas leak monitoring devices, fire/safety detection systems for home, factory and commercial use; Flammable gas leak alarm, gas leak detector, etc.

Features

  • *High sensitivity to C3H8 gas
  • *Excellent anti-interference ability
  • *Excellent stability

Specifications

Model

MPn-5

Sensor Type

Flat surfaced

Standard Encapsulation

Metal cap

Target Gas

Liquefied Gas Sensor

Detection range

300~5250ppm 

Standard Circuit

Conditions

Loop Voltage

Vc

≤24V DC

Heater Voltage

VH

5V±0.1V AC or DC

Load Resistance

RL

Adjustable

Heater consumption

PH

305±25mW

Heater Current

IH

61±5 mA

Sensitive resistance

RS

1KΩ~20KΩ(in 2000ppm C3H8)

Sensitivity

S

Rs(in air)/Rs( 2000ppm C3H8)≥8

Concentration Slope

α

≤0.6(R2000ppm/R500ppm C3H8)

Standard test conditions

Temp.  Humidity

20℃±2℃;55%±5%RH

Standard test circuit

Vc:5V±0.1V; VH: 5V±0.1V

Preheat time

Not less than 48 hours

O2content

21% (not less than 18%)

O2 concentration effects initial value, sensitivity and repeatability.

Lifespan

10 years

* The description and specifications might be changed without notice. Please contact us for the latest information before placing orders.

Technical Support:

Customized technical design and function, LOGO and package are available without extra charge (including molding fee) for mass volume.

The sensors don't have sleeping mode. It can be set in program if needed.

All Winsen products go through strict inspections and tests to make sure they are 100% qualified before shipping out.

The sensor has been fully tested (not calibrated) before leaving the factory, but the module will be calibrated before leaving the factory.

However, after transportation and storage, the environment conditions change, and the surface of the sensor absorbs moisture, mixed gas, pollution matters, etc. It is recommended that customers perform aging and calibration after sensors become stable according to the program and use occasions of the whole device.

15﹪-90﹪RH without condensation,greater or less than this range or long-term high temperature and high humidity will affect the life of the sensor.

Our sensors are certified with CE, 3C, ROHS, anti-explosion, fire prevention, and coal mining safety according to different applications. And we provide assistance for new certification.

Many factors can cause the sensor to fail such as broken wires in transportation, poisoning, falling off of the sensitive material, damage to the heating wire (device), etc. Please find specific cause in each category with Winsen’s aftersales.

Winsen provides professional consultation and service before and after sales. We will recommend the best fitting sensor for your demand. If you have any problem, don’t hesitate to email us to sales@winsensor.com